Home
The RTU-X is a robust electronic device that features digital inputs and outputs, analog inputs, a variety of built-in communication interfaces and protocols, and local programming capability.
It is an ideal product for implementing monitoring, acquisition, and control applications, integrating with an infinite number of sensors, actuators, and IoT platforms.
If this is the first time you are using the device, we recommend visiting the First Steps section.
The device's technical characteristics are described below.
Power supply
| Power | Details |
| Voltage |
|
| Battery | Internal 3.7V Li-Ion battery
|
| Consumption | Normal operation = 120mA Low power = 200uA Battery life for different scenarios can be checked here |
Inputs and outputs
| Input/Output | Details |
| Digital inputs |
Expandable via expansion modules |
| Digital outputs |
Maximum voltage 300V. Maximum current 100mA |
| Analog inputs | 2 configurable 12-bit analog inputs, 0-10V or 0-20mA. 0 - 10V. Input resistance > 1 MOhm. Error < 0.05% FS 0 - 20mA. Input resistance = 100 Ohm. Error < 0.1% FS |
| Power output | Internally generated 12V or 24V DC power, with capacity up to 1A@12VDC or 0.5A@24VDC |
Communication interfaces
| Interface | Details |
| WiFi | 802.11 b/g/n |
| Ethernet | 10BASE-T available by default on the DIN model |
| Bluetooth | BLE v4.2 |
| Cellular modem | NBIOT Modules
LTE Modules
|
| Lora |
|
The device has an SMA connector for an external antenna, which can optionally be used for the cellular modem, the Lora module, and the WiFi and Bluetooth interfaces.
Communication protocols
| Protocol | Details |
| MQTT(S) | JSON, Ultra light 2.0, and Predix packets. TLS encryption. |
| Modbus | Modbus TCP. Modbus RTU over RS-485 (with expansion module). Master of up to 16 devices, or slave. |
| NTP | Time synchronization via Network Time Protocol |
| SDI-12 | SDI-12 interface version 1.4 |
Software
| Function | Details |
| Script | Local programming capability in a C-like language that allows control over every aspect of the device. |
| Log | Internal non-volatile memory to store up to 200,000 time-stamped variables. |
| FOTA | Secure remote updates. |
Physical characteristics
| Characteristic | Details |
| Enclosure |
|
| Dimensions |
|
| Weight | 490g |
| Operating temperature | -30ºC to 60ºC |
Expansion modules
Up to 2 expansion modules can be added.\
| Module | Details |
| Digital input expansion (DIN Module) | 3 dry-contact digital inputs |
| Digital output expansion (DOUT Module) | 3 optoisolated digital outputs. Maximum voltage 300V. Maximum current 100mA |
| Analog input expansion (AIN Module) | 3 configurable 12-bit analog inputs:
|
| RS-485 (RS-485 Module) | Modbus RTU master or slave |
| SDI-12 (SDI-12 Module) | SDI-12 for connecting external sensors |